AI Data Center: Cofinair cuts water consumption by 20% – Valeur Énergie #87

16/11/2026
Cofinair blue and red shape

Featured in Valeur Énergie #87 (October 2026): a case study dedicated to AI Data Center, plus an interview with Andriy Witko, Data Center Development Director at Cofinair.

Valeur Énergie - AI Data Centers

The October 2026 issue of Valeur Énergie (#87) features Cofinair in two articles: a case study on an 80 MW adiabatic cooling installation for an AI data center in France, and an interview with Andriy Witko, Data Center Development Director at Cofinair, on data center cooling in the age of AI. Here are the key points.

AI Data center case study: 80 MW of adiabatic coolers in France

For an AI-dedicated data center in France, Cofinair installed more than 80 MW of adiabatic cooling (30 units of 2.7 MW plus two backups) serving a 36/48 °C liquid-cooling loop, with N+1 redundancy.

By optimizing sizing and control, Cofinair guaranteed fully dry operation up to 28.6 °C, 1.6 °C beyond the 27 °C target. A higher dry threshold limits the time spent in wet mode, and annual water consumption drops by 20% compared with a standard cooler, improving WUE. The trade-off: fan electricity consumption rises by about 11%.

Interview: Andriy Witko on cooling in the AI era

Andriy Witko, Data Center Development Director at Cofinair, highlights the key trends:

  • Higher densities, warmer water. AI racks reach 50–100 kW, and water loops now run at 30/40 °C or 35/45 °C. This makes free cooling particularly relevant and reduces, or even eliminates, the need for mechanical chillers.
  • Better PUE and WUE. Liquid cooling and adiabatic technologies allow new AI data centers to reach a PUE of 1.1–1.3, against a global average of 1.5–1.6, while water use is managed dynamically by favoring dry mode.
  • Hybrid is the norm. Adiabatic coolers are preferred to eliminate Legionella risk, reduce maintenance and minimize water consumption, while cooling towers offer better heat dissipation per m² and suit high-power sites. Hybrid architectures combining both with water/water chillers are becoming standard.
  • Europe’s opportunity. Some estimates suggest the European cooling market could more than double between 2026 and 2031. European manufacturers have strong assets in thermal expertise, proximity to clients and local industrial capacity, and water consumption will become a decisive criterion.